- #01Attachment to existing structureLife Safety
Connection details between the new work and the existing structure must show fastener type, spacing, and embedment.
FBC-B 2002.5FBC-R R301.1 - #02Florida product approvalCode
Florida product approval (FL#) or Miami-Dade NOA must be listed for regulated products (fenestration, structural panels, covering systems).
FBC-B 1708FBC-R R301.2.1.2 - #03Plan review applicability (FBC 107.3.5)Documentation
Per FBC-B 107.3.5, plan review is not required for reroofs (Exemption #2). FCC performs this review only when the building department requires plan review or the client opts in.
FBC-B 107.3.5
Commercial Re-Roof
Last updated: Apr 20, 2026
Section 1
Required Documents
Submit these with your initial project package.
Always required
- Construction Plans Sealed by a Florida Registered Design ProfessionalRoofing plans sealed by a Florida-registered design professional
- Product ApprovalsFlorida Product Approvals for underlayment and roofing materials
- Roof Sheathing & Dry-In AffidavitSigned affidavit for roof sheathing and dry-in inspection compliance
Conditional
- Structural Engineer VerificationStructural engineer verification that the new roofing system does not exceed existing structural capacityWhenRequired if the new roofing system results in a weight increase of more than 10% over the existing system
Section 2
Plan Review Criteria
What FCC's plans examiner looks for on this project type, by trade. Items are grouped by priority — life-safety first. Building department checks may go further; this is the FCC private provider scope under FL Statute 553.791.
BuildingAdvisory
Items marked Advisory are non-blocking. Per FBC 107.3.5, plan review isn't required for these scopes — FCC reviews them when the building department requests it or the client wants the extra set of eyes.
Section 3
Inspection Walkthrough
Inspections are listed in their typical phase order. Your FCC inspector will confirm which apply to your project. Call (772) 222-6679 with questions.
Building
Roof Dry In, In Progress
Required- Underlayment installationCritical
Verify roof underlayment type and installation per code and manufacturer specs
FBC-R R905.1.1 - Drip edge installationCritical
Verify drip edge is installed at eaves and rakes
FBC-R R905.2.8.5 - Valley and flashingCritical
Verify valley flashing and wall flashing are properly installed
FBC-R R903.2 - Roof penetration sealing
Verify all roof penetrations are properly sealed and flashed
FBC-R R903.2 - Deck conditionCritical
Verify roof deck is in acceptable condition and any damaged sheathing has been replaced
FBC-R R803.1
Roof Final
RequiredTypical Final- Roofing material installationCritical
Verify roofing material is installed per manufacturer specs and approved plans
FBC-R R905.2 - Flashing completenessCritical
Verify all flashing is complete at walls, valleys, penetrations, and edges
FBC-R R903.2 - Ridge vent or ventilation
Verify roof ventilation is installed per plans
FBC-R R806.1 - Nailing pattern complianceCritical
Verify roofing material nailing pattern meets high-wind requirements
FBC-R R905.2 - Cleanup and debris removal
Verify job site is clean with no exposed nails or debris in gutters
FBC-B 110.3