- #01Structural attachment and uplift (MF solar)Life Safety
Racking attachment designed for wind uplift; fastener embedment per engineering.
FBC-B 1607.13ASCE 7 - #02Roof load and fire access (MF solar)Life Safety
Existing roof must support added solar load; firefighter pathways preserved per FBC-R R324.
FBC-B 1603FBC-R R324.4 - #03Engineer of record sealDocumentation
Structural drawings must bear a current Florida-licensed engineer's seal and signature.
Florida Statutes Chapter 471FBC-B 107.3.5
Multi Family Solar
Last updated: Apr 20, 2026
Section 1
Required Documents
Submit these with your initial project package.
Always required
- Construction Plans Sealed by a Florida Registered Design ProfessionalSolar installation plans including structural attachment details, equipment specifications, and electrical diagrams. Must include product/equipment specs.
- Site SurveySite survey or plan showing solar panel layout, roof orientation, and property boundaries
Section 2
Plan Review Criteria
What FCC's plans examiner looks for on this project type, by trade. Items are grouped by priority — life-safety first. Building department checks may go further; this is the FCC private provider scope under FL Statute 553.791.
BuildingRequired
ElectricalRequired
- #01PV disconnect and rapid shutdown (MF)Life Safety
NEC 690.12/690.13 disconnect and rapid shutdown.
NEC 690.12NEC 690.13 - #02Grounding, bonding, and interconnection (MF solar)Life Safety
PV grounding/bonding per NEC 690.41-.47 and interconnection per 705.12.
NEC 690.41NEC 705.12
Section 3
Inspection Walkthrough
Inspections are listed in their typical phase order. Your FCC inspector will confirm which apply to your project. Call (772) 222-6679 with questions.
Electrical
Rough Electrical
Required- Mounting and racking systemCritical
Verify solar panel mounting and racking system is installed per engineered plans with proper roof attachment
FBC-B 1603.1FBC-R R324.4 - Electrical conduit and wiringCritical
Verify conduit routing, wire sizing, and connections per approved plans and NEC
NEC 690.31NEC 690.8 - Grounding and bondingCritical
Verify equipment grounding conductor and bonding of all metallic racking components
NEC 690.43NEC 690.47 - Rapid shutdown complianceCritical
Verify rapid shutdown system is installed and labeled per NEC
NEC 690.12 - Roof penetration waterproofingCritical
Verify all roof penetrations are properly flashed and sealed
FBC-R R903.2
Final Electrical
RequiredTypical Final- Panel installation and layoutCritical
Verify solar panel layout matches approved plans and all panels are secured
FBC-R R324.4 - Inverter installationCritical
Verify inverter is properly installed with required clearances and labeling
NEC 690.8NEC 705.12 - Disconnect and labelingCritical
Verify AC and DC disconnects are installed, accessible, and properly labeled
NEC 690.13NEC 690.56 - System operational test
Verify system powers on and produces expected output
NEC 690.1