- #01Wind-borne debris protectionLife Safety
In the Wind-Borne Debris Region, glazed openings must be impact-rated or protected by an approved shutter/panel system.
FBC-R R301.2.1.2FBC-B 1609.2 - #02Egress from sleeping roomsLife Safety
Each sleeping room must have an emergency escape and rescue opening meeting R310 dimensions.
FBC-R R310 - #03Fire-rated unit separationLife Safety
Dwelling-unit and corridor separations must maintain the original fire-resistance rating through any new work.
FBC-B 420FBC-B 711FBC-B 708 - #04Florida product approvalCode
Florida product approval (FL#) or Miami-Dade NOA must be listed for regulated products (fenestration, structural panels, covering systems).
FBC-B 1708FBC-R R301.2.1.2
Multi Family Window/Door Replacement
Like for like window and/or door replacement with no modification to existing openings
Last updated: Apr 20, 2026
Section 1
Required Documents
Submit these with your initial project package.
Always required
- Product ApprovalsFlorida Product Approvals for replacement windows and/or doors showing impact rating, design pressure, and NOA/FL number
Conditional
- Construction Plans Sealed by a Florida Registered Design ProfessionalStructural engineering plans sealed by a Florida-registered professional engineerWhenRequired if structural changes are involved (new openings, enlarged openings, header modifications)
- Opening Modification GuidanceWindow/door replacement project type applies to replacement within existing openings only.WhenGuidance only (non-blocking at intake): if opening sizes/locations are modified, submit under an Alteration project type.
Section 2
Plan Review Criteria
What FCC's plans examiner looks for on this project type, by trade. Items are grouped by priority — life-safety first. Building department checks may go further; this is the FCC private provider scope under FL Statute 553.791.
BuildingRequired
Section 3
Inspection Walkthrough
Inspections are listed in their typical phase order. Your FCC inspector will confirm which apply to your project. Call (772) 222-6679 with questions.
Building
Buck, Flashing
RequiredBD-DependentMost jurisdictions skip this inspection for this project type. Confirm with your building department whether they'll require it.
- Buck and flashing installationCritical
Verify window/door bucks and flashing are properly installed per manufacturer specs
FBC-R R703.4FBC-B 1710.3 - Anchor and fastener patternCritical
Verify anchoring method and fastener spacing per manufacturer installation instructions
FBC-B 1710.2FBC-B 1710.4 - Sealant and weatherproofing
Verify sealant is applied per manufacturer specs at all joints
FBC-R R703.4
Final Building
RequiredTypical Final- Window/door product approvalCritical
Verify installed windows and doors have valid Florida Product Approval matching approved plans
FBC-R R609.3FBC-B 1710.2 - Window/door operationCritical
Verify all windows and doors open, close, lock, and seal properly
FBC-R R612.1 - Impact rating verificationCritical
Verify impact-rated products where required by wind zone
FBC-R R301.2.1.2FBC-B 1710.1 - Egress complianceCritical
Verify bedroom windows still meet egress size requirements after replacement
FBC-R R310.1 - Interior and exterior finish
Verify interior trim and exterior caulking are complete
FBC-R R703.4