- #01Asbestos / lead paint assessmentLife Safety
Pre-demolition asbestos survey is required by federal NESHAP rules for most structures. Lead paint assessment required for pre-1978 dwellings disturbing painted surfaces.
40 CFR 61 Subpart M40 CFR 745 (RRP Rule)FBC-B 107.3.5 demolition - #02Adjacent property protection and utility disconnectsLife Safety
Demolition plan should identify utility disconnect responsibilities and adjacent-property protection for shared walls or close structures.
FBC-EB 1401Local demolition standards - #03Plan review applicability (FBC 107.3.5)Documentation
FBC-B 107.3.5 identifies asbestos removal as the only minimum plan review criterion for demolition. Full plan review for SF demolition is typically BD-discretionary. FCC performs this review only when the building department requires plan review or the client opts in.
FBC-B 107.3.5
Single Family Demolition
Demolition of an existing single family home, duplex, or townhome
Last updated: Apr 20, 2026
Section 1
Required Documents
Submit these with your initial project package.
Always required
- Demolition Plan or Detailed Scope of WorkDemolition plan or detailed written scope of work describing all demolition activities
- Site Plan / SurveySite plan or survey showing structures to be demolished and surrounding features
Conditional
- Asbestos SurveyAsbestos survey guidance based on year built and risk; verify requirement during downstream review as needed.WhenGuidance only (non-blocking at intake): may be required depending on year built and asbestos risk factors.
Section 2
Plan Review Criteria
What FCC's plans examiner looks for on this project type, by trade. Items are grouped by priority — life-safety first. Building department checks may go further; this is the FCC private provider scope under FL Statute 553.791.
BuildingAdvisory
Items marked Advisory are non-blocking. Per FBC 107.3.5, plan review isn't required for these scopes — FCC reviews them when the building department requests it or the client wants the extra set of eyes.
Section 3
Inspection Walkthrough
Inspections are listed in their typical phase order. Your FCC inspector will confirm which apply to your project. Call (772) 222-6679 with questions.
Building
Final Building
RequiredTypical Final- Structure fully demolishedCritical
Verify permitted structure is completely demolished and removed from site
FBC-B 110.3 - Utility disconnectionCritical
Verify all utilities (electric, gas, water, sewer) are properly disconnected and capped
FBC-B 3303.5 - Site conditionCritical
Verify site is graded, debris is removed, and no hazardous materials remain
FBC-B 3303.3 - Erosion control
Verify erosion control measures are in place if required
FBC-B 3303.2