- #01Attachment to existing structureLife Safety
Connection details between the new work and the existing structure must show fastener type, spacing, and embedment.
FBC-B 2002.5FBC-R R301.1 - #02Florida product approvalCode
Florida product approval (FL#) or Miami-Dade NOA must be listed for regulated products (fenestration, structural panels, covering systems).
FBC-B 1708FBC-R R301.2.1.2 - #03Flood panel product approval and installation per manufacturerCode
Flood panel must be installed per Florida product approval or manufacturer instructions.
FBC-B 1612FBC-B 1708 - #04Plan review applicability (FBC 107.3.5 minimum criteria)Documentation
Standalone flood panel installation is a flood-mitigation sub-scope. FCC performs this review only when the building department requires plan review or the client opts in.
FBC-B 107.3.5
Single Family Flood Panel Installation
Last updated: Apr 21, 2026
Section 1
Required Documents
Submit these with your initial project package.
Always required
- Florida Product Approval (Flood Panel/Barrier)
- Installation Details / Anchor Schedule
- Site Plan / Survey
Section 2
Plan Review Criteria
What FCC's plans examiner looks for on this project type, by trade. Items are grouped by priority — life-safety first. Building department checks may go further; this is the FCC private provider scope under FL Statute 553.791.
BuildingAdvisory
Items marked Advisory are non-blocking. Per FBC 107.3.5, plan review isn't required for these scopes — FCC reviews them when the building department requests it or the client wants the extra set of eyes.
Section 3
Inspection Walkthrough
Inspections are listed in their typical phase order. Your FCC inspector will confirm which apply to your project. Call (772) 222-6679 with questions.
Building
Final Building
RequiredTypical Final- Product approval verificationCritical
Verify flood panels have valid Florida Product Approval or engineering matching approved plans
FBC-B 1612.1 - Track and mounting installationCritical
Verify mounting tracks and anchors are installed per manufacturer specs and engineering
FBC-B 1612.1 - Panel fit and sealCritical
Verify panels fit properly in tracks with complete seal against water intrusion
FBC-B 1612.1 - Coverage of all required openingsCritical
Verify all openings below flood elevation are protected per approved plans
FBC-B 1612.4