- #01Footing / foundation designLife Safety
Footing or foundation design must show dimensions, reinforcement, depth, and connection to the structure above.
FBC-R R403FBC-B 1809 - #02Attachment to existing structureLife Safety
Connection details between the new work and the existing structure must show fastener type, spacing, and embedment.
FBC-B 2002.5FBC-R R301.1 - #03Florida product approvalCode
Florida product approval (FL#) or Miami-Dade NOA must be listed for regulated products (fenestration, structural panels, covering systems).
FBC-B 1708FBC-R R301.2.1.2 - #04Plan review applicability (FBC 107.3.5)Documentation
Per FBC-B 107.3.5, pre-manufactured / prototype plans are exempt except for local site adaptation, foundations, and modifications (Exemption #5). FCC performs this review only when the building department requires plan review or the client opts in.
FBC-B 107.3.5
Single Family Pre-Manufactured Shed Installation
Last updated: Apr 20, 2026
Section 1
Required Documents
Submit these with your initial project package.
Always required
- Manufacturer Plan SpecificationsManufacturer plan/spec package including wind load criteria and anchor method.
- Site Plan / SurveySite plan or survey showing property boundaries, setbacks, and shed location.
Section 2
Plan Review Criteria
What FCC's plans examiner looks for on this project type, by trade. Items are grouped by priority — life-safety first. Building department checks may go further; this is the FCC private provider scope under FL Statute 553.791.
BuildingAdvisory
Items marked Advisory are non-blocking. Per FBC 107.3.5, plan review isn't required for these scopes — FCC reviews them when the building department requests it or the client wants the extra set of eyes.
Section 3
Inspection Walkthrough
Inspections are listed in their typical phase order. Your FCC inspector will confirm which apply to your project. Call (772) 222-6679 with questions.
Building
Footing, Slab, UFER
ConditionalInspection criteria coming soon — your FCC inspector will walk you through this inspection on-site.
Final Building
RequiredTypical Final- Shed placement and setbackCritical
Verify shed is placed per approved site plan with proper setbacks from property lines and structures
FBC-R R301.1 - Anchoring and tie-downCritical
Verify shed is anchored per manufacturer specs or engineering for wind zone
FBC-R R301.2.1 - Electrical connection (if applicable)
If wired, verify electrical connection is properly made per plans
NEC 225.30 - Overall condition
Verify shed is level, undamaged, and matches approved plans
FBC-B 110.3