- #01Wind-borne debris protectionLife Safety
In the Wind-Borne Debris Region (WBDR), glazed openings must either be impact-rated or protected by an approved shutter/panel system.
FBC-R R301.2.1.2FBC-B 1609.2 - #02Egress window compliance (bedrooms)Life Safety
Any replacement window serving a sleeping room must meet emergency escape and rescue opening requirements: clear opening area, width, height, and sill height.
FBC-R R310 - #03Florida product approval for each fenestration productCode
Each new window and door must carry a Florida product approval (FL#) or Miami-Dade NOA suitable for the project's wind zone and application.
FBC-B 1708FBC-R R301.2.1.2FBC-R R609 - #04Plan review applicability (FBC 107.3.5 / 107.3.4.2)Documentation
Fenestration replacement is not included in the FBC-B 107.3.5 minimum plan review criteria for one- and two-family dwellings. Contractor certification under FBC-B 107.3.4.2 is an accepted pathway for wind-resistance compliance. FCC performs this review only when the building department requires plan review or the client opts in.
FBC-B 107.3.5FBC-B 107.3.4.2 - #05Flashing and weather-resistive barrier integrationPerformance
Installation details should show flashing at head, jambs, and sill, integrated with the existing weather-resistive barrier.
FBC-R R703.4FBC-B 1404.4
Single Family Window/Door Replacement
Like for like window and/or door replacement with no modification to existing openings
Last updated: Apr 20, 2026
Section 1
Required Documents
Submit these with your initial project package.
Always required
- Product ApprovalsFlorida Product Approvals for replacement windows and/or doors showing impact rating, design pressure, and NOA/FL number
Conditional
- Floor Plan Showing Opening LocationsA floor plan or elevation with the windows/doors being replaced clearly marked. A marked-up photo or simple sketch is often sufficient.WhenRequired only if your building department asks for it. Many jurisdictions do not require this for straight replacements.
- Opening Modification GuidanceWindow/door replacement project type applies to replacement within existing openings only.WhenGuidance only (non-blocking at intake): if opening sizes/locations are modified, submit under an Alteration project type.
Section 2
Plan Review Criteria
What FCC's plans examiner looks for on this project type, by trade. Items are grouped by priority — life-safety first. Building department checks may go further; this is the FCC private provider scope under FL Statute 553.791.
BuildingAdvisory
Items marked Advisory are non-blocking. Per FBC 107.3.5, plan review isn't required for these scopes — FCC reviews them when the building department requests it or the client wants the extra set of eyes.
Section 3
Inspection Walkthrough
Inspections are listed in their typical phase order. Your FCC inspector will confirm which apply to your project. Call (772) 222-6679 with questions.
Building
Buck, Flashing
RequiredBD-DependentMost jurisdictions skip this inspection for this project type. Confirm with your building department whether they'll require it.
- Buck and flashing installationCritical
Verify window/door bucks and flashing are properly installed per manufacturer specs
FBC-R R703.4FBC-B 1710.3 - Anchor and fastener patternCritical
Verify anchoring method and fastener spacing per manufacturer installation instructions
FBC-B 1710.2FBC-B 1710.4 - Sealant and weatherproofing
Verify sealant is applied per manufacturer specs at all joints
FBC-R R703.4
Final Building
RequiredTypical Final- Window/door product approvalCritical
Verify installed windows and doors have valid Florida Product Approval matching approved plans
FBC-R R609.3FBC-B 1710.2 - Window/door operationCritical
Verify all windows and doors open, close, lock, and seal properly
FBC-R R612.1 - Impact rating verificationCritical
Verify impact-rated products where required by wind zone
FBC-R R301.2.1.2FBC-B 1710.1 - Egress complianceCritical
Verify bedroom windows still meet egress size requirements after replacement
FBC-R R310.1 - Interior and exterior finish
Verify interior trim and exterior caulking are complete
FBC-R R703.4